Register to unlock your exclusive B2B prices. Register now
Combined arrester Type 1+2+3 DEHNventil M2 four-pole f. TN-S systems w image 1
Combined arrester Type 1+2+3 DEHNventil M2 four-pole f. TN-S systems w image 2
Combined arrester Type 1+2+3 DEHNventil M2 four-pole f. TN-S systems w image 3

Combined arrester Type 1+2+3 DEHNventil M2 four-pole f. TN-S systems w

In stock price (excl. VAT):
1 493,14 €
This price is valid until 2024-12-31
Price per m: 1 493,14 €
EAN: 4013364400894
MPN: 954405
Our warehouse: No Vendor stock: No
Per package: 1 Per box: 1 Per pallet: N/A
Technical data
Item condition New
Manufacture name Combined arrester Type 1+2+3 DEHNventil M2 four-pole f. TN-S systems w
Brand Dehn
Categories Lighting protection
Country of origin DE
Harmonized System Code 8536 3090 00
Mounting method DIN rail (top hat rail) 35 mm
Lightning impulse current (10/350 µs) 100 kA
Number of poles 4
Construction size 4 modular spacing
Remote signalling Yes
Follow current extinguishing capability 50 kA
Max. continuous voltage AC 255 V
Nominal voltage AC 230 V
Test class Type 1 and 2 and 3
Signalling at the device Optic
Degree of protection (IP) IP20
Voltage protection level N-PE 1.5 kV
Max. conductor cross section solid (solid, stranded) 35 mm²
Max. conductor cross section flexible (fine-strand) 25 mm²
Specific energy (W/R) 2500 kJ/Ohm
Energy-coordinated protection effect with regard to the terminal equipment Yes
System configuration TN-S Yes
Voltage protection level L-PE 1.5 kV
Max. overcurrent protection device, parallel connection (fuse) 250 A
Max. overcurrent protection device, series connection (fuse) 100 A
Voltage switching spark gap technology Yes
Packing details
Packing level 1 4013364400894, 4013364400894
Downloads
Description
Multipole, spark-gap-based, modular DEHNventil combined arrester type 1 + type 2 + type 3 according to EN 61643-11, consisting of a base part and a plug-in protection module. Maximum system availability due to rapid arc control (RAC) spark gaps. Capable of protecting terminal equipment. For protecting low-voltage consumer installations against surges and even direct lightning strikes. For installation in conformity with the lightning protection zone concept at the boundaries from 0A – 2.

Accessories