Item condition | New |
Manufacture name | OVR ZP+ 3N 12.5-255 Surge Protective Device |
Brand | ABB |
Categories |
Lighting protection |
Harmonized System Code | 8536 9095 00 |
Mounting method | Busbar |
Lightning impulse current (10/350 µs) | 12.5 kA |
Number of poles | 4 |
Construction size | 2 modular spacing |
Voltage protection level | 1.5 kV |
Remote signalling | No |
Follow current extinguishing capability | 25 kA |
Max. continuous voltage AC | 255 V |
Nominal voltage AC | 230 V |
Test class | Type 1 + 2 |
Voltage protection level L-N | 1.5 kV |
Signalling at the device | Optic |
Degree of protection (IP) | IP30 |
Voltage protection level N-PE | 1.5 kV |
Integrated backup fuse | No |
Max. conductor cross section solid (solid, stranded) | 35 mm² |
Max. conductor cross section flexible (fine-strand) | 50 mm² |
Energy-coordinated protection effect with regard to the terminal equipment | No |
System configuration DC | No |
System configuration IT | No |
System configuration TN | Yes |
System configuration TN-C | No |
System configuration TN-S | Yes |
System configuration TT | Yes |
System configuration other | No |
System configuration TN-C-S | Yes |
Voltage protection level L-PE | 1.6 kV |
Max. overcurrent protection device, parallel connection (fuse) | -1 A |
Max. overcurrent protection device, series connection (fuse) | -1 A |
Voltage switching spark gap technology | No |
Overcurrent protected voltage tapping | No |
Packing level 1 | 3660308528001 |
Packing level 2 | 3660308528001 |