Trunking for E-Line 7651 Fix IP64 LED continuous line applications. To simplify installation, a pre-assembled continuous line coupler is included in the scope of delivery for connection to a further trunking unit. Length of the trunking: 2996 mm. With 7-conductor through-wiring. Cable cross-section 2.5 mm2. With 2 female connectors for tool-free, electrical connection of the gear trays at 1500 mm intervals. With 7-pole plug/socket pair for rapid electrical connection and termination at ends with protection against accidental contact. The heat-resistant through-wiring is factory-completed with all necessary components. All connections are designed for fast connection and are with reverse polarity protection. The trunking body is made of hot-dip galvanised sheet steel. The coating thickness of 20 μm (Z 275 according to DIN EN 10346) guarantees a corrosion protection of up to 33 years when using the trunking profile in environments according to corrosiveness category C3 according to DIN EN ISO 12944-2. Surface coated silver-grey.