Technical Information
Prekės būklė |
Nauja |
Gamintojo pavadinimas |
Motor circuit breaker, TeSys GV4, 3P, 115A, Icu 50kA, thermal magnetic multifunction, lugs terminals |
Prekės ženklas |
Schneider Electric
|
Kategorijos |
Variklio apsaugos jungtuvai
|
Kilmės šalis |
PL |
Suderintos sistemos kodas |
8536 2090 90
|
Plotis |
81 mm |
Aukštis |
155 mm |
Gylis |
116 mm |
Nominali operacinė galia, kai AC-3, 400 V |
55 kW |
Su integruotu papildomu jungikliu |
No |
Nominali nuolatinė srovė Iu |
115 A |
Su integruotu per žemos įtampos jungikliu |
No |
Polių skaičius |
3 |
Nominali operacinė įtampa |
0-690 V |
Apsaugos nuo perkrovos diapazono nustatymas |
65-115 A |
Saugos laipsnis (IP) |
IP40 |
Su termine apsauga |
Yes |
Pagrindinės srovės grandinės jungties tipas |
Varžto jungtis |
Kontrolinio elemento tipas |
Pavalko svirtis |
Išjungimo metodas |
Elektroninis |
Nominali operacinė galia, kai AC-3, 230 V |
30 kW |
Nominalus trumpo jungimosi atjungimo pajėgumas Icu, kai 400 V, AC |
50 kA |
Reguliuojamo diapazono neuždelstas trumpo jungimosi atjungimas |
1955 A |
Jautrus faziniams gedimams |
Yes |
Įrenginio konstrukcija |
Pilnas prietaisas korpuse |
Pakavimo informacija
Pakavimo lygis 1 |
3606481310941 |
Atsisiuntimai
Aprašymas
TeSys GV motor circuit breaker, 3 poles (3P), 115A/690V, for protection of 3-phase motors 37-55kW@400V. Multifunction circuit breaker, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 50kA@400V, start-stop control by toggle, connection for bars or cables with lugs. Thermal protection adjustable by dials with a setting current Ir in range 65-115A and a selectable tripping class 10 or 20, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).