Technical Information
Prekės būklė |
Nauja |
Gamintojo pavadinimas |
PM3250 power meter - RS485 |
Prekės ženklas |
Schneider Electric
|
Kategorijos |
Automatika ir valdymas
|
Kilmės šalis |
CN |
Suderintos sistemos kodas |
9028 3090 00
|
Montavimo metodas |
Sumontuotas |
Plotis |
0 mm |
Modelis |
Matavimo transformatorius |
Aukštis |
0 mm |
Įtampos tipas |
Kintamoji ar nuolatinė srovė |
Matuojama atminties vertė |
No |
Rodmuo/indikacija |
Skaitmeninis |
Dažnio matavimas |
Yes |
Maks. srovė (Imax) |
6 A |
Reaktyvi energija |
Yes |
Tikslumo klasė |
0.5 |
Aukščiausio parametro matavimas |
Yes |
Matavimo diapazonas |
80-570 V |
Galios faktorius |
Yes |
Naudingoji galia |
Yes |
Regima galia |
Yes |
Laiptelio kampas (cos phi) |
No |
LON palaikomas protokolas |
No |
Modbus palaikomas protokolas |
Yes |
Maksimali saugojama vertė |
Yes |
Minimali saugoma vertė |
Yes |
Su komunikacijos sąsaja RS 485 |
Yes |
Poliškumas |
3 laidininkai/4 laidininkai |
Apkrovos profilio matavimas |
No |
Nominali srovė (In) |
5 A |
Su ryšio sąsaja KNX |
No |
Su ryšio sąsaja pagal EN 62056-21 |
No |
Su ryšio sąsaja M-Bus |
No |
Pakavimo informacija
Pakavimo lygis 1 |
3606480481604 |
Pakavimo lygis 2 |
3606480481602 |
Pakavimo lygis 3 |
3606480481604 |
Atsisiuntimai
Aprašymas
PM3250 DIN mount energy meter with a 128 by 96 pixel backlit, LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 32 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor, Apparent Power, Total Harmonic Distortion and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 277VAC, 173 to 480VAC and 100 to 300VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase, Single Phase and Neutral or Three Phase configurations. Direct measurement range is 50 to 570VAC, with an external VT 570 to 999000VAC. The range of measurement voltage between Phases is 80 to 570VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 50 to 330VAC at 45 to 65 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter offers event recording with up to 5 alarms. Product dimensions are as follows: width 3.54 in (90 mm), depth 2.76in (70 mm), height 3.74 in (95 mm) and product weight 9.17 oz (260 g).